Conceptual design of a building with columns and shear walls
1.
| Criteria | a | b | c | |
| Restraint of floor shrinkage | observation | full restraints at all corners | corners are left free but restraints along the edges | non-uniform retraints |
| conclusion | option (a) will have high restraint to shrinkage , thus lead to cracks in floor | its average | it will not effectively restraint the shrinkage ,so possibly less cracks | |
| The lateral stiffness | observation | comparatively lower lateral stiffness in both x & y | uniform & comparatively higher lateral stiffness in both x & y | non uniform lateral stiffness in both x & y |
| conclusion | it will provide higher lateral stiffness for pure seismic acceleration in X & y direction | |||
| torsion with respect to vertical axis | observation | corner walls provide more resistance to twist | edge walls provide good resistance to twist | irregular walls provide poor resistance to twist |
| conclusion | its is best | its worse | ||
| vertical reinforcement for similar base capacity | observation | walls are subjected to nominal flexural and heavy twisting moment | walls are subjected to nominal twisting moment | walls are subjected to heavy flexural and heavy twisting moment |
| conclusion | it requires least | it requires higher vertical reinforcement | ||
| static eccentricty | observation | structurally symmetric | structurally symmetric | un symmetric |
| conclusion | it will have static eccentricity & its significant | |||
| system redundancy | observation | uniform placements of lateral load supports in both axes | uniform placements of lateral load supports in both axes | concentrated lateral load supports in both axes |
| conclusion | its more redundant | its more redundant | less redundant | |
| foundation system | observation | Due to L shaped walls , geometry of foundation and design will be critical | walls are in line. Easy to fix the geometry and design of foundation | walls are in line & conentrated . Easy to fix the geometry and design of foundation |
| conclusion | it recommended to have peripherical box foundation | it should be incorporated with isolated /strip footing | it should be incorporated with isolated /strip footing | |
| Architectural constraints | observation | walls obstruct only corners | walls obstruct the faces of the building | vertical wall will not allow passage |
| conclusion | its preferred | subjected to discussion | not recommended |
2. issue in the given framing plan:
Indirect lateral load transfer in X & Y directrions: The beam is connected to another beam which are ineffective during lateral load transfer. in such conditions, primary beam is prone to shear failure.
Eccentricity :
The longer the distance between center of mass and center of stiffness , the higher the torsional moment of the building. As per the given plan eccentricity , the building is subjected to higher torsional moment (torsional flexibility) in both X & Y direction
Strong beam Weak column possibility
The sizes of column majorly mentioned as 25cm*25cm , but all the beams have much deeper sections 50cm. Inertia of beams is visually higher than the column. if the column reinforcement is adequatelt greater than that of the beams , it ok and since we do not have reinforcement details , this is doubtful. it is recommended to have slightly bigger sizes of column.
3. floor plan - The floor plan of the building is not either uniform or symmetric . so naturally any lateral load induced in the floor will not have 100% influence in same direction. Definitely a special lateral load resisting system for these torsional moments should be accomodated.
Random interanl columns- Since internal columns are random , they are unable ton transfer lateral loads effectively and can not achieve desirable building response . so we have to assume and design those columns for only gravity loads
Floor to Floor variations in partition walls and beams- partition walls provide an important mass control in a building and beams play key role in shear transfer from floor to beam. All these elements are not in order. So heavy distortion and distribution of lateral loads will hapen.
Suggestions on lateral load system &its foundation
Heavy torsional forces should be controlled by respective lateral load system. So corner shear walls are suggested
The proportion of floor area is greater on left side than the right side (irregular quadrilateral) . So corner shear walls on the left side should be heavier than the right.
corner shear walls shall preferably be supported over a box foundation. Shear walls should be connected by link beams to transfer shear from one to other.
The internal columns shall be supported by isolated footing. Those isolated footing can be connected with shear walls through tie beams.