Distribution Systems and Load, Demand and Plant Factor Example
A free lesson from Skill-Lync's Introduction to Electric Power System course, on Grow by Skill-Lync · Last updated 16 Nov 2026 · Session: “Week 1 Session 3”
What will you learn in this free Introduction to Electric Power System lesson?
The instructor describes the distribution system and compares radial, parallel feeder and ring main layouts, then discusses the unsettled 230 V versus 240 V standard in India. He defines load, demand, diversity and plant factors and works one example from a daily load curve.
- Radial, parallel feeder and ring main layouts
- Reliability and cost trade-offs of each layout
- Load factor: average load over peak load
- Demand and plant factor from a load curve
What comes after lesson 3?
Later in Skill-Lync's Introduction to Electric Power System course (paid): lesson 4, Week 1 Session 4; lesson 5, Week 2 Session 1; lesson 6, Week 2 Session 2. The full course has 51 lessons (22 h 21 min of video); see the course overview or its price and syllabus.
Lesson transcript
Machine transcript of the lesson audio (lightly cleaned). Technical terms may contain errors; the video is the reference.
Hello guys, welcome to session 3 of week 1 module. In the session 2, we have discussed the technical details of the power system. We have discussed the power system structure and we have also seen that in the power system, there are three main components. These are the generation system, transmission system and distribution system. About generation system and transmission system, we have discussed in the session 2. We have seen the various technical details of the generation and transmission system. about the types of different generation power plants and the types of transmission system in the session 2.
Now, in session 3, we will go through the third main component that is the distribution system. We will also cover some technical terms associated with power system network. So, to begin with the session 3, let's start with the distribution system. So, as we know, distribution system is the part of electric power system which connects the end user of energy to the main grid lines. So, basically, it works as the connecting medium between the loads and the transmission system. In the distribution system, they are mainly connected with a step down transformer.
Because, as we know, at the transmission level, the voltage are very high. But, at the distribution side or at the load side, we don't need that high voltage. We would need the low voltage levels. That's why a step down transformer is required between the transmission and the distribution system. The first electrical distribution system was developed by Thomas Edison. It was an underground direct current system. The distribution system usually employs equipments such as transformers, circuit breakers and some protective devices. The most of the distribution system are radial in nature.
With radial, I mean here that from one end to other end, there is no loops or they all are connected in series. There are no parallel feeders. So, that's why in the distribution system, the most of the distribution network are radial in nature. So, now moving further, the types of distribution system. Here, we can see the first type of the distribution system that is radial feeder. As I have already told that most of the distribution system are radial in nature. We can see from this diagram that there is a distribution feeder.
Here, we can see there is a high voltage substation. From that high voltage substation, there is a single low voltage feeder. From this low voltage feeder, at different points, the different loads are connected. Here, in this example figure, we can see that there is only one substation or there is only one point from where we are receiving the power. From this one point, there is one feeder, that is a low voltage feeder. And from this low voltage feeder, at three points, the loads are connected via a step-down transformer.
So, we can see there is the direction of power flow is unidirectional. means the power is flowing in one direction only. That is from this substation to various loads. It has the lowest initial cost and simple structure. But the drawback with radial type of distribution system is if there is a fault in the system, then it can lead to the complete failure of the supply. Here, we can see if a fault happens at this section of low voltage feeder, then if the circuit breaker opens at this point, then the load connected after this circuit breaker, like this load, the second complete load and the third complete load, they all will get disconnected from the main substation and the power supply will be hampered.
That is the main drawback with the radial type of distribution system. Now, moving towards the next type of distribution system, that is the parallel feeder. In the radial feeder, we have seen there is a risk of complete failure of system to all load. To overcome that drawback in the parallel feeder, it has been proposed that instead of only one feeder, we can have two parallel feeder. Here, we can see the service station is only one, so means the power is coming from this direction and the load is connected to the other end of the feeder.
Here, the direction of power flow is again only one, means the power is flowing from service station to load only. In this parallel feeder, we can see instead of the power flow is unidirectional from generating service station to the load service station, but we have two parallel feeders connected between them. So, to reduce the system failure risk, one more line is added here. We can see if there is a fault in the feeder one and the circuit breaker connecting the feeder one to both the service station opens, then the load at the other end of the feeder will continuously get the supply with the help of feeder two.
So, it increases the system reliability and it is more beneficial than the radial feeder system or the radial type of distribution system. So, this is all about the parallel feeder system. Now, moving towards the next type of distribution system that is the ring main distribution system. In the ring main distribution system, there it may have one or more than one generating stations. Here, we can see this type of distribution system. It looks like a ring shape. Here, the power flow can be in both the direction.
We can see the generating station is here, but it can have or it can be at the same time at this place also or at this place also. So, the power can flow from this bus to that load in this direction or the power can flow from this bus to this load in this direction. So, in this way, we can see with the ring main distribution system, the power flow can be multi-directional. Here, multiple generating stations and multiple loads can be connected. It can have more than four buses or it can have any number of buses.
The reliability of this type of distribution system is very high. That's why it is also very highly dependable system. We can see if the fault happens at this line, which means the line is open now, but the load connected at this bus can continuously get the power from the alternate path that is following this route. In the same way, if any one line gets out of the system, then the other component connected in the system can get the power or can send the power to the other component via some.
So, in the same way, save this area. Thank you. alternate path. So that is the main advantage with the ring main type of distribution system that it gives multiple path for the power flow. This is all about the distribution system. Now moving towards the Indian distribution system as we all know that in India the distribution voltage level is some 230 or 250. Now here is a question for you all that at what voltage level we get power in our homes whether it is 230 volt or 240 volts. As we know in Indian distribution system what is the Indian standard for the distribution voltage level. So let me give you a brief history what is the voltage level in Indian distribution system.
So in 1988 the Indian standard termed as IS12360 they fixed the voltage band for the electrical installation including preferred voltages and frequency. They fixed the AC voltage level of AC. They fixed the AC voltage for the low transmission system. Low transmission system here we mean that the distribution system. So the preferred nominal AC voltage is specified as 240 volts line to ground voltage and 415 volts line to line voltage. But with the recommendations of some technical experts in 2012 the amendment 1 has been proposed. In the amendment 1 it has been proposed that the voltage level should be reduced from 240 volts to 230 volts.
It has been accepted and it has been planned that the complete transition of this reducing the voltage should be completed in 3 years. But after the 6 years the complete transition has not been happened. So again in 2006 the amendment 2 has been proposed. So again in 2006 the amendment 2 has been proposed. In this amendment it has been proposed that the transition of lowering the voltage from 240 volts to 230 volts should be completed by December 2007. By the end of 2007. By the end of 2009 this has not been happened. And then again in 2009 and 2011 the amendment 3 and amendment 4 has been proposed.
And the transition of voltage from 240 volts to 230 volts has not been completed. So finally in 2011 the changeover of the system voltage from 240 volts to 230 volts shall be kept in advance for the time being. So that is the problem. So that is the problem that now we have some state electricity boards companies and private utilities they are using 230 volts and 400 volts while there are some electricity boards and companies they are using 240 volts. So in India it is still a confusion. What is the Indian standard of distribution voltage whether it is 230 volts or 240 volts. Let me tell you what is the problem if there is no fixed standard for the voltage level.
So if you check your domestic appliance and the lightning fixture you will find that most of these equipments have the voltage rating marked as 230 volts. It means with the 10 percent tolerance they should be able to sustain a supply voltage of 207 voltage or the maximum of 253 voltage. However as per the prevailing Indian standard which specifies the minimum voltage as 240 volts. The discom or the distribution companies in India requires to maintain the voltage level within 216 voltage at the minimum side and 264 voltage at the maximum side.
So now assume a situation that the supply voltage is around 260 volts and your appliance fails. In this situation the appliance manufacturer can say that he has no liability because the voltage was too high. While on the other hand the distribution company can get away by arguing that the voltage was within the permissible range. So that is the situation in India that the voltage for the distribution level or for the distribution system is not yet finalized whether it should be 230 volts or 240 volts. So now moving further to some technical aspect in the power system network that is some key factors and terms associated with the power system network.
Here we know that the power system network is a very complex system. Its network and its other components all are having some parameters. They have some values. So with the help of those parameters we have defined some factors or some terms. These factors and terms are helpful in management and the planning of the power system. If we are planning for a new transmission line or if we are planning for a new generation plant or if we are planning for a new load. In all those cases these factors and terms plays an important role in defining the rating and the capacity of all these components.
So there are various terms and factors for defining the power system operating characteristics. They basically depend on load and generation parameters. So based on the load and generation parameters they are divided in two categories. The first one is load related terms and the second one is generation related terms. Now moving one by one the load related and the generation related terms. The first one is the load related terms. At the load side we can see that how much total load is connected. That term is known as the connected load. The sum connected load is defined as the sum of rated capacity of all the electrical devices connected to the supply.
At the load side there is another term that is known as maximum demand. Maximum demand is the greatest value of demand which has occurred during the specified period of time. There is another term that is demand factor. Demand factor is the ratio of maximum demand to the total connected load. There is another factor that is the load factor. Load factor is the ratio of average load divided by peak load. In the load related terms. In the load related terms there are few other factors which defines how the loads are diversity. What is the diversity of the load. So that diversity is defined by the diversity factor. It is the ratio of sum of individual maximum demand to the coincident maximum demand.
So if you are talking about the coincident factor. So if you are talking about the coincident factor. So it is the ratio of coincident maximum demand divided by the sum of individual maximum demand. In the same way the load diversity. How the load diversity is defined. It is sum of individual maximum demand minus coincident maximum demand. So these are all load related terms. Now moving further to the generation related terms. In the generation related terms. In the generation related terms. They are all basically related to a single power plant. So for a single power plant. The plant capacity. It is the maximum rated capacity of a power plant.
To deliver during its peak operation. In the same way. The plant factor. For a single power plant. The plant factor is defined as. The ratio of actual energy produced. During a particular. Time t to the plant capacity multiplied by that particular time t. In the same way, the utilization factor for a power plant is defined as the ratio of maximum demand of a system to the rated generation capacity of the system. So, these are the generation related terms. So, now we have seen the factors and terms related to the load side and the generation side. Now, we can have an example to understand all these terms. What are their significance? What they represent? We are going to discuss an example here.
Here, here we can see our load curve. Here, we can see in this graph, the x-axis is time. The x-axis is time in hour and it is for one complete day. That is the 24 hours. And on the y-axis, the load demand is there. The load demand is in megawatt. We can see for the time duration from 0 to 8 hours. The load is 2 megawatt. So, here in the table, it is given from this table, we have plotted this graph using MATLAB. So, from time 0 to 8 hours, the load is 2 megawatt. From 8 hours to 12 hours, the load demand is 4 megawatt. From 12 hours to 22 hours, the load demand is 6 megawatt. In the same way, from 22 to 24 hours, the load demand is again 2 megawatt.
Now, the total load or the total connected load is given as 10 megawatt. And the capacity of the generating unit is given as 8 megawatt. Now, we have to calculate the different load parameters and the generating parameters for this complete system. So, to calculate the average load, we have to calculate the area under this graph. Here, we can see, if we calculate the area under this graph, we can get the value of average load. Now, to calculate the area under the curve, we can divide the complete curve into 4 segments.
This is the first segment, where the length is 8 and the width is 2. So, 2 into 8. In the second segment, the length is 4 and the width is also 4. This is the third segment, the length is 10 and the width is 6. So, that's why it is 10 multiplied by 6. This is the fourth segment, the length is 2 and the width is also 2. So, if we calculate this area under the curve, it comes as 96. So, this is the energy or it is the units of electrical energy that has been consumed during that complete one day.
So, it is coming out as 96 megawatt hour. Now, what is the average load? As we have calculated in earlier slide, that total energy consumed in that particular time, divided by that particular time. So, it is 96 as we have calculated in my previous slide, that 96 is the total energy consumed, divided by the total time, that is the 24 hours. As we can see, it comes as 4 megawatt. So, it means the average load is 4 megawatt. Now, the load factor. As from the definition, we have seen that the load factor is the ratio of average load and the peak load.
The peak load from the graph, we have seen it is 6 megawatt and the average load as we have calculated here, it is 4 megawatt. So, which comes as the load factor, which comes as the load factor, 0.667. Same as we can calculate the demand factor, we know from the definition of demand factor, it is the ratio of maximum demand to the total connected load. In the example, it has been given that the total connected load is 10 megawatt and maximum demand from the curve, we have seen it is 6 megawatt.
So, this value comes as 0.6. Now, calculating the plant factor, the plant factor, as we have already seen, it is the ratio of actual energy produced during a particular time divided by the plant capacity multiplied by that particular time. In the example, it has been given that the plant capacity is 8 megawatt and the time duration of our study is 24 hour. So, in the denominator, it is 8 multiplied by 24 and in the numerator, we have to put the actual energy produced. The actual energy produced should be equal to the actual energy consumed.
So, here it is 96 megawatt hour, which we have calculated earlier with the help of the area under the curve. So, it comes as 0.5 as the plant factor. So, here we have calculated all the factors and here we have seen how these factors related to the load and the generation side can be calculated with the help of one example. So, in this session, we have discussed about the distribution system, different types of distribution system. their benefits and their shortcomings, we have discussed that various terms and factors related with load and the generation side like demand factor, load factor, diversity factor and at the generation side like plant factor, plant capacity.
So, all these factors we have studied, their significance we have studied and we have also done an example to show how to calculate all these values. So, this is all about the session 3, we have discussed all these things. Now, in the session 4 of the week 1 module, we will further discuss about the various power system studies and what are the simulation softwares we have, which includes some licensed softwares and some open source softwares also. So, in the session 4, we will discuss about the various power system studies, various power system softwares and we will also see one MATLAB example for the power system study.