Design of Tension Member

Q.1 Net Area for tension member calculation problem.

Soln:

i) Plate Drilled Hole,

We know, Net section area = (b - nd)t

Given, b = 260mm : t = 20mm

d = 20 mm but, do = 20+2 = 22mm

n = 4

therefore, An = (260 - 4(22))20 = 3440mm2

ii) Plate – Zigzag bolting,

We know, Net section area = (b - nd + sum(P2/4g))t

Given, b = 260mm t = 20mm

d = 20 mm but, do = 20+2 = 22mm

* Case 1: Along section AD or BF : An = (260 - 2(22))20 = 4320mm2

* Case 2 : Along section CEG : An = (260 - 3(22))20 = 3880mm4

* Case 3 : Along section ACEG : An = (260 - 4(22) + 60^2/4(60) )20 = 3740mm2

* Case 4 : Along section BCEG : An = (260 - 4(22) + 50^2/4(60) )20 = 3648.33mm2

* Case 5 : Along section ACF : An = (260 - 3(22) + 60^2/4(60) + 50^2/4(60))20 = 3948mm2

The minimum value is the net section area, Hence An = 3648.33 mm2

iii) Anlge (200 x 100 x 12 with M20 bolt)

Solution:

We know, Net section area = (b - nd + sum(P2/4g))t

Given:

angle section: 200mmX100mm : t = 12mm

d = 20 mm but, do = 20+2 = 22mm

An = (200+100 - 3(22) + 50^2/4(90) + 50^2/4(130) ) 12

An = 2949.02mm2

Q.2 Sag rod design problem.

Soln:

Consider, center-to-center distance between rafters of 8 meters, with a purlin spacing of 1.2 meters.

* The roofing system, including thermal insulation, has a self-weight of 60 kg/m².

* The wind pressure intensity is 150 kg/m². The rafter slope is set at 15 degrees, and there is a live load of 75 kg/m².

* The assumed self-weight of the purlin is 100 kg/m.

Solution:

DL + LL = (60+75)*9.8*1.2*8 = 12700

Load on each sag rod = (12700/3 + 100*9.8*8/3)Sin(15) = 6846.66*Sin(15) = 1772 N

Therfore, we know

Load on threaded rod, Tdn= 0.9*An*fu/1.25

1772 = 0.9*An*fu/1.25

An = 1772*1.25/(0.9*250) (fu = 250 Mpa)

An = 9.844

d = (4*An/pi)^0.5

d = 3.54 mm

Q.3 Determine section size for given tensile load.

Soln:

Assume 4mm weld size , fy = 250MPa, fu = 410 Mpa

Approximate gross area = 1.1Tdg/fy = 1.1 x 250 x 1000/250 = 1100 mmA2

* From steel table, select ISA 100x75x8mm connected to gusset plate by longer length Cxx

Area of connected leg = ( 100 - 8/2) x 8 = 768mm2

Area of outstanding leg = ( 75 - 8/2) x 8 = 568mm2

Ag = 768+568 — 1336mm2 > 1100mm2 ,hence Safe.

* Design strength due to yielding of gross section,

Tdg = Agfy/rmo = 0.91 x 1336 x 250 11000 = 303.94kN

* Design strength due to rupture at net section,

Tdn = alpha*An*fu/rml

fu = o.8x1336x410/1000

fu = 438.21 KN

* Design strength due to block shear, for calculation of block shear, length of weld is required

P1 x 100 = 250 x (100 -31) = 172.50KN

P2 = 250 - 172.50 = 77.5 KN

Strength of 4mm weld = 0.7 x 4 x 0.462 x 410 = 530.37 kn/mm

Effective length of weld on head side = 172.5 x 1000/530.37 = 325mm

Effective length of weld on toe side = 77.5 x 1000/530.37 = 146mm

Total welded length = 325 + 146 = 471mm

Avg = Avn = 471 x 8 = 3768 mm2

Atg = Atn = 100 x 8 = 800mm2

Tdb1 = 0.525Avg x fy + 0.72 x Atn x fy = 0.525 x 3768 x 250/1000 + 0.72 x 800 x 410/1000 = 730.31kN

Tdb2 = 0.416 Avn x fu + 0.91 x Atg x fy = 0.416 x 3768 x 410/1000 + 0.91 x 800 x 250/1000 = 824.67KN

Tensile strength provided = 438.21kN, 303.94KN and 730.71KN > 250KN

Hence safe.