Challenge

Reinforcement detailing of Columns from ETABS output

Ans:-

Aim:- To provide the longitudinal Reinforcement of the columns from foundation to Terrace level and to sketch the column cross sectional and elevation details in Autocad.

To show the shear reinforcement and lapping details as per Clause 8.1 of IS 13290-2016.

Introduction:

1.in the first step the given model is Set for run option.

2.Once the Analysis is completed, then the concrete frame design option is clicked.

3.Now the under the concrete frame design option select the option display design info and click longitudinal Reinforcement.

4.Longitudinal reinforcement will be visible, note the values of the reinforcement required.

4.In the next Step note down the shear reinforcement details.

  1. Start the design and detailing.

COLUMN DESIGN
COLUMNS ALONG THE GRID 3A Column dimension 450*650
1 Longitudinal Reinforcment calculation
a) Minimum Reinforcment 0.8% of Gross cross sectional Area 2340 mm^2
As per clause no.26.5.3.1 of Is 456 2000
b) Maximum Reinforcment 6% of Gross cross sectional Area 17550 mm^2
As per clause no.26.5.3.1 of Is 456 2000
c) Maximum Ast along 3 A 6938 mm^2
As per clause no.26.5.3.1 of Is 456 2000
Dia of the longitudinal Reinforcment should 12 mm or more
There for using 16 mm dia bars
Dia of bar 32
Area of 1 bar 804.352
number of bars 8.625576862
There fore using 8 number of 32 mm dia bars Ast 6434.816
Remaning Ast Ast 503.184
There for using 16 mm dia bars
Dia of bar 20
Area of 1 bar 314.2
number of bars 1.601476766
There fore using 2 number of 20 mm dia bars Ast 628.4
There fore total longitudinal reinforcment provided
8 no. of 32 mm dia bars
2no. Of 20 mm dia bars
Ast provided 7063.216 mm^2
The spacing between the longitudinal bars should not exceed 300mm.
2 Shear Reinforcment calculation
a) Minimum dia for shear Reinforcment for 32 mm dia 8 mm
As per clause no 7.4.2 of IS 13290- 2016
b) Maximum Shear reinforcment from the Etabs out put 720.48 mm^2
c) There for using 8 mm dia bars mm^2
Dia of bar 8
Area of 1 bar 50.272
Special confining reinforcement clause no 8 of IS 13290 2016
The special cofining reinforcement shall be provided at lo.
lo should not be less tham
larger lateral dimension of the column 650mm
1/6 of the clear span of member 554.1666667
450 mm 450
There fore lo = 650 mm
The spacing of shear reinforcment along lo should not be more than
a 1/4 of minimum dimension of beam/column
minimum dimension of column 450 mm
1/4th of minimum dimension of column 112.5 mm
b 6 times the dia of smallest longitudinal reinforcement bar
Dia of smallest longitudinal reinforcement bar 20 mm
6 times the dia of smallest longitudinal reinforcement bar 120 mm
c 100 mm 100 mm
There fore for special confining reinfrocemnet #8mm @100 mm c/cis provided in the lo zone.
Transverses Reinforcment calculation for the zone upto h/4.
hc in m Beam depth h
Height of the column of Plinth level column 1.5 0.5 1
Height of the column ofGF column 4 0.5 3.5
Height of the column of FF column 3.45 0.5 2.95
Height of the column of SF column 3.45 0.5 2.95
Height of the column of TF column 3.45 0.5 2.95
3.45 0.5 2.95
h h/4 approximate
Plinth level 1 0.25 300 mm
GF 3.5 0.875 900 mm
FF 2.95 0.7375 900 mm
SF 2.95 0.7375 900 mm
TF 2.95 0.7375 900 mm
Transverse reinforcement in the splice Zone as per clause number 7.4.of IS 13290 2016
As per the clause nuo. 7.4.1 of IS 13290 2016 the ends should have 135 hook with an
extension of 6d of bars.
d 32 mm
6d 192 mm
As per the clause nuo. 7.4.2 of IS 13290 2016
a 8 mm dia bars are used in stirrups if the dia of longitudinal bars is less than or equal to 32 mm
b The maximum c/c spacing of stirrups is 300 mm
c a cross tie should be provided if the dimension of the column exceeds 300 mm.
There fore upto h/4 #8mm @300 mm c/cis provided in the lo zone.
As per the clause no. 7.3.2.1 of IS 13290 2016
100 mm spacng should be provided within this splicing zone
There fore in the splice zone #8mm @100 mm c/cis provided in the lo zone.
For the columns terminating in the footing
as per clause nummber 8.2 of IS 13290 2016.
special confinement reinforcement should be provided upto 300 mm or larger length inside the footing.
COLUMNS ALONG THE GRID 3B Column dimension 450*650
1 Longitudinal Reinforcment calculation
a) Minimum Reinforcment 0.8% of Gross cross sectional Area 2340 mm^2
As per clause no.26.5.3.1 of Is 456 2000
b) Maximum Reinforcment 6% of Gross cross sectional Area 17550 mm^2
As per clause no.26.5.3.1 of Is 456 2000
c) Maximum Ast along 3 A 5022 mm^2
As per clause no.26.5.3.1 of Is 456 2000
Dia of the longitudinal Reinforcment should 12 mm or more
There for using 16 mm dia bars
Dia of bar 28
Area of 1 bar 615.832
number of bars 8.154821445
There fore using 8 number of 32 mm dia bars Ast 4926.656
Remaning Ast Ast 95.344
There for using 16 mm dia bars
Dia of bar 16
Area of 1 bar 201.088
number of bars 0.474140675
There fore using 2 number of 20 mm dia bars Ast 402.176
There fore total longitudinal reinforcment provided
8 no. of 28 mm dia bars
2no. Of 16 mm dia bars
Ast provided 5328.832 mm^2
The spacing between the longitudinal bars should not exceed 300mm.
2 Shear Reinforcment calculation
a) Minimum dia for shear Reinforcment for 32 mm dia 8 mm
As per clause no 7.4.2 of IS 13290- 2016
b) Maximum Shear reinforcment from the Etabs out put 720.48 mm^2
c) There for using 8 mm dia bars mm^2
Dia of bar 8
Area of 1 bar 50.272
Special confining reinforcement clause no 8 of IS 13290 2016
The special cofining reinforcement shall be provided at lo.
lo should not be less tham
larger lateral dimension of the column 650mm
1/6 of the clear span of member 554.1666667
450 mm 450
There fore lo = 650 mm
The spacing of shear reinforcment along lo should not be more than
a 1/4 of minimum dimension of beam/column
minimum dimension of column 450 mm
1/4th of minimum dimension of column 112.5 mm
b 6 times the dia of smallest longitudinal reinforcement bar
Dia of smallest longitudinal reinforcement bar 20 mm
6 times the dia of smallest longitudinal reinforcement bar 120 mm
c 100 mm 100 mm
There fore for special confining reinfrocemnet #8mm @100 mm c/cis provided in the lo zone.
Transverses Reinforcment calculation for the zone upto h/4.
hc in m Beam depth h
Height of the column of Plinth level column 1.5 0.5 1
Height of the column ofGF column 4 0.5 3.5
Height of the column of FF column 3.45 0.5 2.95
Height of the column of SF column 3.45 0.5 2.95
Height of the column of TF column 3.45 0.5 2.95
3.45 0.5 2.95
h h/4 approximate
Plinth level 1 0.25 300 mm
GF 3.5 0.875 900 mm
FF 2.95 0.7375 900 mm
SF 2.95 0.7375 900 mm
TF 2.95 0.7375 900 mm
Transverse reinforcement in the splice Zone as per clause number 7.4.of IS 13290 2016
As per the clause nuo. 7.4.1 of IS 13290 2016 the ends should have 135 hook with an
extension of 6d of bars.
d 32 mm
6d 192 mm
As per the clause nuo. 7.4.2 of IS 13290 2016
a 8 mm dia bars are used in stirrups if the dia of longitudinal bars is less than or equal to 32 mm
b The maximum c/c spacing of stirrups is 300 mm
c a cross tie should be provided if the dimension of the column exceeds 300 mm.
There fore upto h/4 #8mm @300 mm c/cis provided in the lo zone.
As per the clause no. 7.3.2.1 of IS 13290 2016
100 mm spacng should be provided within this splicing zone
There fore in the splice zone #8mm @100 mm c/cis provided in the lo zone.
For the columns terminating in the footing
as per clause nummber 8.2 of IS 13290 2016.
special confinement reinforcement should be provided upto 300 mm or larger length inside the footing.

7.column detailing drawings

Your portfolio, next

Ship work like this
in your own course.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.