concrete mix design for M35 grade concrete with fly ash:

i)stipulations for proportioning of M35 grade concrete-

a) grade of designation- M35

b) type of cement - OPC 53

c)type of admixture- fly ash

d)maximum nominal size of aggregate - 20mm

e)minimum cement content - 340kg (table 5-IS456)

f)maximum cement content- 450(as per code)

g)partial replacement of cement by fly ash- 30%( as per requirement)

h)maximum W/C ratio- 0.45(table5:IS456)

I)workability-100mm

j) chemical admixture - PCS type

ii)test data for materials -

a)cement used -OPC 53-confirming to IS 8112

b)specific gravity of cement- 3.15- test-IS:2720

c)mineral admixture -fly ash -confirming to IS12089

d)specific gravity of fly ash - 2.90

f)chemical admixture- @0.6% - IS9103

e)specific gravity of - - test -IS2386

coarse aggregate - 2.74

fine aggregate -2.74

admixture PCE based -1.12

g) water absorption - test-IS 2386

coarse aggregate - 0.5%

fine aggregate - 1%

h)sieve analysis - test -IS2386

Coarse aggregate _-confirming to table 2- IS383

Fine aggregate - zone II- confirming to table4- IS 383

iii)target strength for mix proportions of M35 grade concrete:

Fck=fck+1.65s( "s" from table 1- IS 10262)

Fck =35+1.65*5=43.25N/mm2

iv) selection of water - cement ratio :

maximum W/C ratio = 0.45(table 5-IS 456)

adopted W/C ratio =o.45

v)selection of water content:

maximum water content =186L (table 2- is1026)

above water content is for 25 to 50mm slump , but we need 100mm slump for our concrete as per specification. so we need to increase the water content to the required slump . clause 4.2 of IS1026 suggests to increase 3% of water content to get an extra 25mm slump. hence we need to increase water content by 6% to get an additional 50mm slump for our concrete.

water content for 100mm slump =186+(0.06*186)=197.16L

since we are using superplasticizers water content can be reduced inorder to get strength in concrete . the amount of water content to be reduce depends on the type of superplasticizer.

percentage of reduction in water content = 20%

water content requirement after SP=198-(0.20*198)=157.73

adopted water content =160L

vi)calculation of cement and fly ash content :

adopted water cement ratio=0.45

total cementitious (cement+fly ash)requirement= water content /water cement ratio=160/0.45=355.55kg

since flyash is used the amount of cementitious content(cement+ flyash) shall be increase to get good workability and strength.the percentage of cementitious content to be increased depends upon the experience and reasearch.here we have increase the cementitious content by 10%.

final cementitious content =356*1.10=391.6kg

minimum cement content required for "severe" exposure = 340kg -table 5-IS456

adopted cementitious content=391.6kg>340kg

flyash content requirement =391.6*0.30( 30% replacement)

=117.48~118kg

cement content requirement = cementitious content -flyash =391.6-117.48=274.12

calculation of super [email protected] to the mass of cementitious content= 391.6*(0.6/100)= 2.35kg

vii)coarse aggregate and fine aggregate :

coarse aggregate ratio=0.62 - table 3-IS10262(for W/C=0.5)

coarse aggregate ratio for 0.45 w/c ratio=0.63 9adding 0.01for every decreases 0.05 and vice varsa)

final fine aggregate ratio =(1-0.63)=0.37

viii)mix calculations of M35 grade concrete:

a) volume of concrete = 1cu.m

b)total volume of cement = cement /(s.g *1000)=275/(3.15*1000)=0.087cu.m

c)total volume of fly ash =flyash/ (s.g*1000)= 118/(2.5*1000)=0.041cu.m

d)volume of water =water/(s.g*1000)=160/(1*1000)=0.016cu.m

e)volume of superplasicizers=superplasticizers / (s.g*1000)=2.35/(1.12*1000)=0.002cu.m

f)total aggregates required =a-(b+c+d+e)=1-(0.087+0.041+0.16+0.002)=0.71cu.m

g)coarse aggregate (c.a)=f*c.a ratio*s.g*1000= 0.71*0.63*2.74*1000=1225.6kg

I)fine aggregate (f.a)=f*f.a ratio *s.g*1000=0.71*0.37*2.74*1000=719.8kg

CEMENT FLYASH SAND AGGREGATE WATER AND SUPERPLASTICIZER NEEDED FOR M35 GRADE CONCRETE:

1. cement- 275kg

2. flyash -118kg

3. fine aggregate -720kg

4. coarse aggregate - 1226kg

5. water - 160L

6.PCE Based superplasticizer- 2L

to find the design mix ratio divide the calculated value of all materials by the weight of cement . there for mix ratio of M35 grade concrete by weight is=cment:flyash:F.A:C.A:water=1:0.4:2.6:4.46:0.58

Your portfolio, next

Ship work like this
in your own course.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.