Project 2
AIM:
To design the worst-case column and its isolated footing from the given framing plan using IS 456:2000 and SP 16 charts. Check for adequacy under combined axial and moment loading, and ensure safe pressure distribution within the permissible soil bearing capacity.
GIVEN
-
Framing plan: 4 bays of 3 m (short span), 3 bays of 8 m (long span)
-
Worst-case column: Interior column supporting largest tributary area
-
Slab live load: 4 kN/m²
-
Slab dead load: 3.75 kN/m²
-
Concrete grade: M30 (column), M25 (footing)
-
Steel grade: Fe415
-
Allowable bearing capacity of soil: 100 kN/m²
-
Depth of footing below ground: 2 m
SOLUTION:
Step 01: Load on Worst-Case Column
-
Tributary area = 8 m × 6 m = 48 m²
-
Total service load = (4 + 3.75) × 48 = 372 kN
-
Factored load (1.5 × 372) = 558 kN
-
Assume 10% self-weight of footing: Total design load = 558 × 1.1 = ~614 kN
Step 02: Column Design (Using SP 16)
-
Size assumed: 300 mm × 500 mm
-
Factored axial load (Pu): 486 kN
-
Ultimate moment (Mu): 80 kNm
-
Non-dimensional parameters:
-
The point lies well within the SP 16 Chart 44 curve, Column design is safe.
Step 3: Footing Area and Size
-
Allowable pressure = 100 kN/m²
-
Required area:
A=100614=6.14m2
Adopt footing size: 2.6 m × 2.4 m = 6.24 m²
-
Net pressure:
, Safe
Step 4: Footing Thickness & Reinforcement
(i) Bending Moment at face of column:
-
Projection: 1.3 m – 0.15 m = 1.15 m
-
Bending moment,
Effective depth (d):
M=0.138⋅fck⋅b⋅d2
d=222mmAdopt effective depth = 250 mm, total depth ≈ 300 mm
(ii) Shear Check at d from face of column:
-
Shear span = 1.15 – 0.25 = 0.9 m
-
Shear force =
-
Nominal shear stress:
-
Permissible shear stress (M25, 0.5% steel):
Safe in shear, no shear reinforcement needed
(iii) Reinforcement (Flexural):
-
-
-
Provide: 12 mm bars @ 150 mm c/c in both directions
Step 05: Column Interaction Curve Summary:
Refer attached image of graph,
-
Factored Axial Load (Pu): 486 kN
-
Assumed Ultimate Moment (Mu): 80 kNm
-
Column Size: 300 mm × 500 mm
-
Concrete Grade: M30
-
Steel Grade: Fe415
Non-Dimensional Parameters:
Design point lies well within the interaction curve based on SP 16 Chart 44 approximation. Column is safe under combined axial and bending loads.
RESULT:
-
Interior column carrying Pu = 486 kN and Mu = 80 kNm is safe using SP 16.
-
Footing size of 2.6 m × 2.4 m is adequate for soil capacity of 100 kN/m².
-
Footing thickness = 300 mm, effective depth = 250 mm
-
Provide 12 mm ⌀ bars @ 150 mm c/c in both directions.
-
No shear reinforcement required in slab or footing.
-
Beam B1 needs 2-legged 10 mm stirrups @ 300 mm c/c near supports.