Project 1
Design only a Main Frame with Lean (Grid 2) & Gable Frame without Lean (Grid 15)
Assume purlin load as 8.77 kg/m
Assume Gantry girder wt. = 158.24 kg/m
Assume Rail weight = 53 kg/m
|
Proposed Coil Centre, Chennai |
|||||
|
Sl.No |
Parameter |
Value |
Data From |
Remark |
|
|
AREA-01 |
|||||
|
Building Parameters |
|||||
|
1 |
Building Width |
30000.00 mm |
Client |
Out to Out of Steel |
|
|
2 |
Width Module |
Clear Span |
Client |
||
|
3 |
Building Length |
140000.00 mm |
Client |
Center to Center of Steel Column |
|
|
4 |
Building Height |
11100.00 mm |
Client |
Clear Height from FFL |
|
|
5 |
Roof Slope |
1:10 |
Client |
||
|
6 |
Column Base |
Fixed Base |
Assumed |
To control Deflection |
|
|
7 |
Bay Spacing (in mm) Main frame with Rafters |
14@10000 |
Client |
Center to Center of Steel Column |
|
|
8 |
Roof Bracing |
Diagonal Angle Bracing |
Client |
||
|
9 |
Wall Bracing |
Portal Bracing and above Angle Bracing |
Client |
Up to 6.5m Portal Bracing |
|
|
10 |
End Wall Type |
Rigid Frame |
Assumed |
||
|
End Wall |
|||||
|
1 |
LEW Bay Spacing |
9800+10400+9800 |
Assumed |
Out to Out of Steel |
|
|
2 |
REW Bay Spacing |
9800+10400+9800 |
Assumed |
Out to Out of Steel |
|
|
Sheeting Specifications |
|||||
|
1 |
Roof Sheeting |
Single Skin Panel |
Client |
0.55mm Galvanized Standing Seam Panel |
|
|
2 |
Wall Sheeting |
Single Skin Panel |
Client |
0.5mm Galvanized Painted (CCGL) Panel |
|
|
3 |
Trims & Flashings |
Assumed |
0.5mm Galvanized Painted Trim |
||
|
Wall Sheeting Condtions |
|||||
|
1 |
Near Side Wall |
Brick wall and above Sheeting |
Client |
Up to 2.80m Brick wall from FFL |
|
|
2 |
Far Side Wall |
Opening and above Sheeting |
Client |
Up to 10.60m Open for access to Existing building |
|
|
3 |
Left End Wall |
Brick wall and above Sheeting |
Client |
Up to 2.80m Brick wall from FFL |
|
|
4 |
Right End Wall |
Brick wall and above Sheeting |
Client |
Up to 2.80m Brick wall from FFL |
|
|
Eave Condition |
|||||
|
1 |
Near Side Wall |
Eave Gutter with PVC Downspout |
Client |
||
|
2 |
Far Side Wall |
Eave Gutter with PVC Downspout |
Client |
||
|
Crane System |
|||||
|
1 |
Crane Capacity |
30MT |
Client |
EOT Crane (Pendant Operated) |
|
|
2 |
C/C of Crane Rail |
27410.00 mm |
Assumed |
Approximate dimension |
|
|
3 |
No. of Cranes |
1 |
Client |
||
|
4 |
Run Length |
Full Length |
Client |
Along GL. 1 to 15 B/W C' & D' |
|
|
5 |
Crane Height |
7500.00 mm |
Client |
Top of Crane Beam from FFL |
|
|
6 |
Bracing Below CB |
Portal Bracing |
Assumed |
||
|
7 |
Crane Data |
Crane weight incl. hoist |
35.0 MT |
Assumed |
|
|
No of wheels |
4 |
Assumed |
|||
|
Wheel Base |
5800.00 mm |
Assumed |
|||
|
Bumper distance |
6200.00 mm |
Assumed |
|||
|
Maximum Wheel Load |
262.00 KN |
Assumed |
|||
|
Vertical Impact |
25.00% |
Code |
As per IS 875 |
||
|
Lateral Impact |
20.00% |
Code |
As per IS 875 |
||
|
Longitudinal Impact |
10.00% |
Code |
As per IS 875 |
||
|
Loading Class |
2 |
Assumed |
As per AISC 1989 |
||
|
Crane System |
|||||
|
1 |
Crane Capacity |
20MT |
Client |
EOT Crane (Pendant Operated) |
|
|
2 |
C/C of Crane Rail |
27410.00 mm |
Assumed |
Approximate dimension |
|
|
3 |
No. of Cranes |
1 |
Client |
||
|
4 |
Run Length |
Full Length |
Client |
Along GL. 1 to 15 B/W C' & D' |
|
|
5 |
Crane Height |
7500.00 mm |
Client |
Top of Crane Beam from FFL |
|
|
6 |
Bracing Below CB |
Portal Bracing |
Assumed |
||
|
7 |
Crane Data |
Crane weight incl. hoist |
25.0 MT |
Assumed |
|
|
No of wheels |
4 |
Assumed |
|||
|
Wheel Base |
4500.00 mm |
Assumed |
|||
|
Bumper distance |
5124.00 mm |
Assumed |
|||
|
Maximum Wheel Load |
165.00 KN |
Assumed |
|||
|
Vertical Impact |
25.00% |
Code |
As per IS 875 |
||
|
Lateral Impact |
20.00% |
Code |
As per IS 875 |
||
|
Longitudinal Impact |
10.00% |
Code |
As per IS 875 |
||
|
Loading Class |
2 |
Assumed |
As per AISC 1989 |
||
|
Sl.No |
Parameter |
Value |
Data From |
Remark |
|
|
Crane System |
|||||
|
1 |
Crane Capacity |
15MT |
Client |
EOT Crane (Pendant Operated) |
|
|
2 |
C/C of Crane Rail |
27410.00 mm |
Assumed |
Approximate dimension |
|
|
3 |
No. of Cranes |
1 |
Client |
||
|
4 |
Run Length |
Full Length |
Client |
Along GL. 1 to 15 B/W C' & D' |
|
|
5 |
Crane Height |
7500.00 mm |
Client |
Top of Crane Beam from FFL |
|
|
6 |
Bracing Below CB |
Portal Bracing |
Assumed |
||
|
7 |
Crane Data |
Crane weight incl. hoist |
18.4 MT |
Assumed |
|
|
No of wheels |
4 |
Assumed |
|||
|
Wheel Base |
4500.00 mm |
Assumed |
|||
|
Bumper distance |
5010.00 mm |
Assumed |
|||
|
Maximum Wheel Load |
123.00 KN |
Assumed |
|||
|
Vertical Impact |
25.00% |
Code |
As per IS 875 |
||
|
Lateral Impact |
20.00% |
Code |
As per IS 875 |
||
|
Longitudinal Impact |
10.00% |
Code |
As per IS 875 |
||
|
Loading Class |
2 |
Assumed |
As per AISC 1989 |
||
|
Roof Extension - Far Side wall Along GL-C' |
|||||
|
1 |
Length |
6000.00 mm |
Client |
||
|
2 |
Location |
Far Side wall Along GL-C' |
Client |
||
|
3 |
Slope |
1:10 |
Client |
||
|
4 |
Eave Condition |
Eave Gutter with PVC Downspout |
Client |
||
|
AREA-02 (Lean to) |
|||||
|
Building Parameters |
|||||
|
1 |
Building Width |
5000.00 mm |
Client |
Out to Out of Steel |
|
|
2 |
Width Module |
Clear Span-Monoslope |
Client |
||
|
3 |
Building Length |
30000.00 mm |
Client |
Center to Center of Steel Column |
|
|
4 |
Building Height (GL-D1') |
6000.00 mm |
Client |
Clear Height from FFL |
|
|
5 |
Roof Slope |
1:10 |
Client |
||
|
6 |
Column Base |
Pinned Base |
Assumed |
||
|
7 |
Bay Spacing (in mm) |
3@10000 |
Client |
Center to Center of Steel Column |
|
|
8 |
Roof Bracing |
Diagonal Angle Bracing |
Client |
||
|
9 |
Wall Bracing |
Portal Bracing |
Client |
Up to Full height |
|
|
10 |
End Wall Type |
Rigid Frame |
Assumed |
||
|
End Wall |
|||||
|
1 |
LEW Bay Spacing |
5000.00 mm |
Assumed |
Out to Out of Steel |
|
|
2 |
REW Bay Spacing |
5000.00 mm |
Assumed |
Out to Out of Steel |
|
|
Sheeting Specifications |
|||||
|
1 |
Roof Sheeting |
Single Skin Panel |
Client |
0.55mm Galvanized Standing Seam Panel |
|
|
2 |
Wall Sheeting |
Single Skin Panel |
Client |
0.5mm Galvanized Painted (CCGL) Panel |
|
|
3 |
Trims & Flashings |
Assumed |
0.5mm Galvanized Painted Trim |
||
|
Wall Sheeting Condtions |
|||||
|
1 |
Near Side Wall |
Brick wall and above Sheeting |
Client |
Up to 2.80m Brick wall from FFL |
|
|
2 |
Far Side Wall |
Brick wall and above Sheeting |
Client |
Up to 2.80m Brick wall from FFL |
|
|
3 |
Left End Wall |
Brick wall and above Sheeting |
Client |
Up to 2.80m Brick wall from FFL |
|
|
4 |
Right End Wall |
Brick wall and above Sheeting |
Client |
Up to 2.80m Brick wall from FFL |
|
|
Eave Condition |
|||||
|
1 |
Near Side Wall |
Eave Gutter with PVC Downspout |
Client |
||
|
2 |
Far Side Wall |
Peak trim |
Client |
||
|
GENERAL PARAMETERS |
|||||
|
Loads & Design |
|||||
|
1 |
Dead Load |
0.14 KN/m2 |
Assumed |
||
|
2 |
Coll Load |
0.15 KN/m2 |
Client |
False ceiling load for Roof extension alone |
|
|
3 |
Live Load |
0.75 KN/m2 |
Code |
IS 875 (Part 2) -2015 |
|
|
Sl.No |
Parameter |
Value |
Data From |
Remark |
|
|
4 |
Wind Load |
Wind Speed |
180 KMPH |
Code |
IS 875 (Part 3) - 2015 |
|
K1 = |
1.00 |
Code |
IS 875 (50 years of mean probable design life |
||
|
K2 = |
0.94 |
Code |
IS 875 (Terrain Category 3) |
||
|
K3 = |
1.00 |
Code |
IS 875 (Upwind slope is less than 3°) |
||
|
K4 = |
1.15 |
Code |
IS 875 (Cyclone Zone) |
||
|
Building Condition |
Medium Permeability |
Code |
IS 875 (Part 3) - 2015 |
||
|
Wind co-efficients calculated as per |
Code |
IS 875 (Part 3) - 2015 |
|||
|
5 |
Seismic Zone |
Zone III |
Code |
IS 1893-2015 (Part 4) |
|
|
6 |
Loads applied as per |
IS 875 - 2015 |
Client |
||
|
7 |
Primary Member design |
IS 800 : 2007 |
Client |
||
|
8 |
Cold Form Design |
AISI 2001 |
Assumed |
||
|
Deflection Limits |
|||||
|
1 |
Horizontal Deflection |
Height / 150 |
Code |
IS 800 : 2007 |
|
|
2 |
Vertical Deflection |
Span / 180 |
Code |
IS 800 : 2007 |
|
|
3 |
Crane Level Deflection |
Height / 200 |
Code |
IS 800 : 2007 |
|
|
Surface Treatment |
|||||
|
1 |
Primer |
25 Micron |
Assumed |
Red Oxide Primer |
|
|
2 |
First Coat |
25 Micron |
Assumed |
Epoxy Paint |
|
|
3 |
Second Coat |
25 Micron |
Assumed |
Epoxy Paint |
|
|
Accessories |
|||||
|
1 |
Skylights 2mm Thk. |
14200mm (L) X 1000mm (W) - 28Nos. |
Client |
On Roof |
|
|
2 |
Ridge Ventilator |
600mm Wide-14 Nos |
Assumed |
3.00 m Length |
|
EXPLANATION:Screen shot attached
Result: