Identification of Cracks
1a-
Observation -
- Concrete crushed and the reinforcement exposed.
- Concrete spalled beyond the reinforcement which may be sign of rupture.
- Beam top portion looks safe because of the flange advantage from slab.
- The crack develops from the bottom to top means rebar yielding occurs in support bottom only.
Answer -
- it's form of flexural failure due to reversal of stress during earthquake.
- During stress reversal , support top experiences compression and bottom experiences tension.
- Top compression is managed by slab advantage. Bottom tension was not satisfied by the provided reinforcement.
- Since the reinforcement got yielded, it can not be repaired.
1b - observation -
- Crack along beam column edge.
- Cracks seem to have developed through the structure as it looks much wider.
- Beam looks separated from column at joints .
- Concrete is not severely crushed.
Answer -
- It's beam pull out failure due to insufficient development length of reinforcement in joint.
- During earthquake, the horizontal movement of structure makes this condition worse and detached the beam member from column.
- Providing anchorage length between two existing concrete is very difficult. So not repairable
1c -
observation -
- Crack are exactly at the joint of the column beam .
- Cracks in beam developed through its entire width.
- Slab also developed more cracks along the beam width direction.
Answer -
- It's a plastic hinge failure.
- The damage occurred only in the joint zone first of all .
- Cyclic lateral loading and stress reversal at the joints led to the damage.
- Even the slab participated to its best to handle the tension( slab is severely cracked means has undergone tension with its flange conditions. )but unable to control the damage.
- The joint can be strengthened.
2a -Observation
- concrete damaged at top of a column.
- concrete damaged all around the column face.
- beam are safe .
- The location of column looks at edge of the building.
- no walls are built along the column means it is probably at ground floor , for parking car movement access.
Answer-
- its a soft failure, technically plastic hinge formation.
- due to the absence of infill walls at the ground floor, the plastic hinge forms at the top of ground story columnss during lateral movement.
- based on the development of crush concrete, it can either be repairable or non repairable.
2b - observation
- concrete developed complete breakage diagonally
- longitudinal reinforcements are intact.
- shear reinforcement spacing looks wider(which means probably lesser shear rebar provided).
Answer
- its a pure shear failure.
- inadequate shear reinforcement compels concrete takes all the shear stresses.
2c - Observation
- column failed completely.
- failure at top of column.
- there are two slabs connected to the column, probably one at mid height of the column.
- the wooden piles might be a post failure support after column failed, providing temporary prop to avoid thecollaps of the entire structure.