Identification of Cracks
1(a): Mode of Failure: Flexural failure due to reversal of stress during earthquake
Observations:
- Concrete is crushed and reinforcement is exposed.
- Concrete spalled beyond the reinforcement which may be a sign of rupture.
- The beam top looks safe because of the flange advantage from the slab.
- The crack develops from bottom to top means rebar yielding occurs in the bottom only.
Result:
- During stress reversal, the support top experiences compression and the bottom experiences tension.
- Top compression is managed by slab advantage. Bottom tension was not satisfied by provided by reinforcement.
- Since the reinforcement got yielded, it cannot be repaired.
1(b): Mode of Failure: Pullout failure due to insufficient development length of reinforcement in Joints.
Observations:
- Cracks along Beam-Column edge. The crack is along the beam line and column line.
- Cracks seem to be developed through the structure as it look much wider.
- The beam looks separated from the column at the joints.
- The horizontal member is detached from the vertical column member.
- Concrete is not severely crushed.
Result:
- During an earthquake, The horizontal movement of the structure makes this condition worse and detaches the beam member from the column.
- Providing anchorage length between two existing concrete is very difficult.
- It’s not repairable.
1(c): Mode of Failure: Plastic hinge Failure
Observations:
- Cracks are exactly at the joint of Column-Beam.
- Cracks in the beam developed through its entire width.
- The slab also developed more cracks along the beam width direction.
Result:
- The damage occurred only in the joint zone first of all.
- Cyclic lateral loading and stress reversal at joints led to the damage.
- Even the slab participated its best to handle it, but unable to control the damage.
- The joint can be strengthened.
2(a): Mode of Failure: Soft storey failure
Observations:
- Concrete damaged at the top of a column.
- Concrete is damaged all around the column face.
- The beams are safe.
- The locations of column looks at the edge of the building.
- No walls are built along column means it is probably on the ground floor, for parking car movement access.
Result:
- It is technically a plastic hinge formation.
- Due to the absence of infill walls on the ground floor, the plastic hinge forms at the top of ground storey columns during Lateral movement.
- Based on the development of crush concrete, it can either be repairable or Non-repairable.
2(b): Mode of Failure: Pure Shear Failure
Observations:
- Concrete developed complete breakage diagonally.
- Longitude reinforcements are intact.
- Shear reinforcement spacing looks wider (which means probably lesser shear rebar provided)
Result:
- Inadequate shear reinforcement compels concrete to take all the shear stresses.
2(c): Mode of Failure: Short column Failure
Observations:
- Column failed completely.
- Failure at the top of column.
- There are two slabs connected to the column, Probably one at mid-height of the column.
- The wooden piles must be post failure support after the column failed, providing prop to avoid the collapse of the entire structure.
Result:
- An additional slab. or a beam connected to a. column in midheight leadsto this effect.
- This leads to failure especially if the connection is unintentional and not accounted in design.
- The failure given in this pivcture is not at all repairable.