Challenge

Identification of Cracks

1(a): Mode of Failure: Flexural failure due to reversal of stress during earthquake

Observations:

  • Concrete is crushed and reinforcement is exposed.
  • Concrete spalled beyond the reinforcement which may be a sign of rupture.
  • The beam top looks safe because of the flange advantage from the slab.
  • The crack develops from bottom to top means rebar yielding occurs in the bottom only.

Result:

  • During stress reversal, the support top experiences compression and the bottom experiences tension.
  • Top compression is managed by slab advantage. Bottom tension was not satisfied by provided by reinforcement.
  • Since the reinforcement got yielded, it cannot be repaired.

1(b): Mode of Failure: Pullout failure due to insufficient development length of reinforcement in Joints.

Observations:

  • Cracks along Beam-Column edge. The crack is along the beam line and column line.
  • Cracks seem to be developed through the structure as it look much wider.
  • The beam looks separated from the column at the joints.
  • The horizontal member is detached from the vertical column member.
  • Concrete is not severely crushed.

Result:

  • During an earthquake, The horizontal movement of the structure makes this condition worse and detaches the beam member from the column.
  • Providing anchorage length between two existing concrete is very difficult.
  • It’s not repairable.

1(c): Mode of Failure: Plastic hinge Failure

Observations:

  • Cracks are exactly at the joint of Column-Beam.
  • Cracks in the beam developed through its entire width.
  • The slab also developed more cracks along the beam width direction.

Result:

  • The damage occurred only in the joint zone first of all.
  • Cyclic lateral loading and stress reversal at joints led to the damage.
  • Even the slab participated its best to handle it, but unable to control the damage.
  • The joint can be strengthened.

2(a): Mode of Failure: Soft storey failure

Observations:

  • Concrete damaged at the top of a column.
  • Concrete is damaged all around the column face.
  • The beams are safe.
  • The locations of column looks at the edge of the building.
  • No walls are built along column means it is probably on the ground floor, for parking car movement access.

Result:

  • It is technically a plastic hinge formation.
  • Due to the absence of infill walls on the ground floor, the plastic hinge forms at the top of ground storey columns during Lateral movement.
  • Based on the development of crush concrete, it can either be repairable or Non-repairable.

2(b): Mode of Failure: Pure Shear Failure

Observations:

  • Concrete developed complete breakage diagonally.
  • Longitude reinforcements are intact.
  • Shear reinforcement spacing looks wider (which means probably lesser shear rebar provided)

Result:

  • Inadequate shear reinforcement compels concrete to take all the shear stresses.

2(c): Mode of Failure: Short column Failure

Observations:

  • Column failed completely.
  • Failure at the top of column.
  • There are two slabs connected to the column, Probably one at mid-height of the column.
  • The wooden piles must be post failure support after the column failed, providing prop to avoid the collapse of the entire structure.

    Result:

    • An additional slab. or a beam connected to a. column in midheight leadsto this effect.
    • This leads to failure especially if the connection is unintentional and not accounted in design.
    • The failure given in this pivcture is not at all repairable.