Project

Heating Solution

  1. INTRODUCTION

Over 25% of the ultimate energy consumption within the globe is attributed to households. The households are thereby the arena with the second largest final energy consumption within the globe, which makes the world a central focus area for energy consumption reductions. a method of reducing the energy consumption of households in cold climates is to boost the efficiency of the heating systems. Low-temperature heating provides one promising solution to how this could be done. By reducing the heat temperatures, it's possible to extend the efficiency of warmth production from heating solution. Furthermore, the warmth loss from the distribution systems inside both new and existing buildings is reduced. the very best heating efficiencies are obtained when both supply and return temperatures are as low as possible. Recent research has therefore described the advantages of using heating plant supply and return temperatures as low as 50° C / 20° C. However, while the provision temperature is usually controlled in line with a weather compensation curve, the return temperature is extremely passionate about the planning and operation of the heating plant. This study therefore embarked on to check methods for evaluation of the chance to get a coffee return temperature in heating systems with supply temperatures of 55° C or lower This project, comparative study of building having different floors, walls and circuits. during this work, it'll study the behaviour of building with different combinations of the wall and floors with regard to circuits. The analysis of the building with insulation floors, walls and circuits and having different combinations is meted out by the warmth load. the entire modelling and analysis are done by using LOOPCAD 2019.

1.1 Materials and methods

1.1.1 Materials

The materials used in the constructions of various models. The materials used for floors are as follows- Concrete Thin Slab, Gypsum Thin Slab, Heat Transfer Plate; Circuits are as follows- Counterflow, Serpentine, Modulated Spiral; Walls are as follows- Frame Wall or Partition Wall, Foam Concrete Matrix, Block Wall.

1.1.2 Floors

  • Concrete Thin Slab- A concrete slab could be a common structural element of contemporary buildings, consisting of a flat, surface product of cast concrete. Steel-reinforced slabs, typically between 100 and 500 mm thick, are most frequently accustomed construct floors and ceilings. In many domestic and industrial buildings, a thick concrete slab supported on foundations or directly on the subsoil, is employed to construct the bottom floor. These slabs are generally classified as ground-bearing or suspended. A slab is ground-bearing if it rests directly on the muse, otherwise the slab is suspended. For multi-story buildings, there are several common slab designs. Beam and block, also said as rib and block, is usually utilized in residential and industrial applications. This slab type is formed from pre-stressed beams and hollow blocks and are temporarily propped until set, typically after 21 days. Standard weight of concrete thin slabs adds about 8.6 kg per sq ft (at 1.5” thickness).
  • Gypsum Thin Slab-There are several methods of putting in hydronic radiant heat systems over a traditional wood-framed floor. one in every of the foremost common is termed a skinny slab system. Thin slabs contains either a specially formulated concrete or poured gypsum underlayment. Both forms of slabs have installation requirements that has got to be carefully coordinated with the building design process. One requirement that has got to be accommodated is that thin-slabs typically add 1.25 to 1.5 inches to the ground height. Another issue that has got to be addressed is that the added weight of the thin-slab. Poured gypsum thin-slabs typically add 5.8 to 6.8 kg per square measure to the “dead loading” of a floor structure
  • Heat Transfer Plate- Heat Transfer Plates are employed in so called “staple up systems” where the ground is warmed by placing heating tubes underneath the ground. Aluminium material wraps round the heating tube then spreads out and attaches to the underside of the heated floor. the aim of warming system are going to be to form heat within the sort of warm water (in an efficient manner) then transfer that heat. Some process must take that heat aloof from the tubing and apply it to the underside of the ground in order that the ground can heat the world above. Aluminium may be a material that transfers heat exceptionally well but it's expensive, and its use should be carefully balanced against other methods of doing the identical thing, and its application should be optimized for performance and value effectiveness.

1.1.3 Walls

Table 1: R-value and U-Value of respective walls

Walls

R-VALUE

(F° · sq. Ft. · hr/Btu)

U-VALUE

(W/m2K)

Frame wall or Partition wall (Fiberglass)

2.59

0.386

Foam Concrete Matrix

5.18

0.193

Block Wall

0.3

3.316

1.1.4 Circuits

Figure 1 (A) Counterflow (B) Serpentine (C) Modulated spiral

1.1.4 TEST METHOD

Firstly, the location of manifolds in ground floor and first floor are explained briefly, besides this the analysis of all the 27 models which has been divided into 3 cases taking circuits in reference explanatory tables have been made all the models which tells is about the head loss, flow rate and load for all the manifolds; which is used to analyze all the models and bring out the most efficient models among the all-in terms of load.

Distribution Manifolds: the situation of the distribution manifold is vital. Long runs between the manifolds and also the radiant panels can reduce the number of tubing available for the radiant panel and increase the pump capacity requirements. Poor accessibility to the manifold can complicate the installation and servicing of the system. Complicated distribution piping can add cost and complexity to the system. the subsequent criterion should be considered when selecting a manifold location. It should be in a very position that permits the runs to be made to the individual zones without excess leader lengths. Normally, it's best to locate the manifold on an enclosed wall where the tubing are often routed from each side of the wall to the manifold. It should be mounted high enough to allow easy connections from below, particularly in concrete or poured floor underlayment applications where the tubing is embedded and a not easily be moved while connecting or reconnecting the fittings.

The study is being performed using LOOPCAD 2019 in three circuit types, and the results will be compared by using three different cases i.e.; case 1, case 2, case 3. The cases are made in combinations with three different walls and floors including the three circuits types.

Figure 2 Manifold location (A) Ground floor (B) First floor

Table 2 Combination used in models for case 1

Model

Circuit

Floor

Wall

Model 1

Counterflow

Concrete Thin Slab

Frame Wall or Partition Wall

Model 2

Counterflow

Concrete Thin Slab

Foam Concrete Matrix

Model 3

Counterflow

Concrete Thin Slab

Block Wall

Model 4

Counterflow

Gypsum Thin Slab

Frame Wall or Partition Wall

Model 5

Counterflow

Gypsum Thin Slab

Foam Concrete Matrix

Model 6

Counterflow

Gypsum Thin Slab

Block Wall

Model 7

Counterflow

Heat Transfer Plate

Frame Wall or Partition Wall

Model 8

Counterflow

Heat Transfer Plate

Foam Concrete Matrix

Model 9

Counterflow

Heat Transfer Plate

Block Wall

Table 3 Combination used in models for case 2

Model

Circuit

Floor

Wall

Model 10

Serpentine

Concrete Thin Slab

Frame Wall or Partition Wall

Model 11

Serpentine

Concrete Thin Slab

Foam Concrete Matrix

Model 12

Serpentine

Concrete Thin Slab

Block Wall

Model 13

Serpentine

Gypsum Thin Slab

Frame Wall or Partition Wall

Model 14

Serpentine

Gypsum Thin Slab

Foam Concrete Matrix

Model 15

Serpentine

Gypsum Thin Slab

Block Wall

Model 16

Serpentine

Heat Transfer Plate

Frame Wall or Partition Wall

Model 17

Serpentine

Heat Transfer Plate

Foam Concrete Matrix

Model 18

Serpentine

Heat Transfer Plate

Block Wall

Table 4 Combination used in models for case 3

Model

Circuit

Floor

Wall

Model 19

Modulated Spiral

Concrete Thin Slab

Frame Wall or Partition Wall

Model 20

Modulated Spiral

Concrete Thin Slab

Foam Concrete Matrix

Model 21

Modulated Spiral

Concrete Thin Slab

Block Wall

Model 22

Modulated Spiral

Gypsum Thin Slab

Frame Wall or Partition Wall

Model 23

Modulated Spiral

Gypsum Thin Slab

Foam Concrete Matrix

Model 24

Modulated Spiral

Gypsum Thin Slab

Block Wall

Model 25

Modulated Spiral

Heat Transfer Plate

Frame Wall or Partition Wall

Model 26

Modulated Spiral

Heat Transfer Plate

Foam Concrete Matrix

Model 27

Modulated Spiral

Heat Transfer Plate

Block Wall

  1. RESULT AND DISCUSSION

The heating solution, water temperature, total fluid volume, head loss and load comparison of findings for case 1, case 2 and case 3 are accomplished in this chapter by assessing various scenarios with different walls, floors and circuits.

The comparison of different models in case 1 is done by loopcad 2019 software is shown in Table 5, Table 6 and Table 7

The G+1 structure is carried out in three circuits types i.e.; Circuit 1, circuit 2 and circuit 3 by using LOOPCAD 2019 software. Comparative study of building wall having different size of the opening and it will also compare the behavior of building with different walls and floor insulations. In this work, it will study the behavior of building with different size and thickness of the wall. Building without insulation wall and floor and building with an insulation walls and floors will have a different condition.

Table 5 Head loss and load comparison in case 1

Model

Head Loss

Load(W)

Model 1

14.6

8262

Model 2

15.1

7456

Model 3

34.3

10662

Model 4

17.6

8262

Model 5

15.1

7456

Model 6

31.3

10398

Model 7

17.4

8562

Model 8

14.7

7456

Model 9

32.8

10753

Table 6 Head loss and load comparison in case 2

Model

Head Loss

Load(W)

Model 10

17.9

8369

Model 11

15.4

7563

Model 12

45.7

13621

Model 13

17.9

7188

Model 14

15.4

6382

Model 15

37.4

12252

Model 16

17.8

8369

Model 17

15.2

7563

Model 18

16.1

9563

Table 7 Head loss and load comparison in case 3

Model

Head Loss

Load(W)

Model 19

24.3

7308

Model 20

21.3

7551

Model 21

28.3

13396

Model 22

26.9

9002

Model 23

19.03

6713

Model 24

21.2

9563

Model 25

23.1

8163

Model 26

21

10662

Model 27

45.7

13621

2.1 Discussion of different models in case 1

Since we can conclude from the table 1, about the R-value & U-value of the walls. Greater the R-value greater will be the insulating power. Above result, we get the same temperature at same environment condition and same energy production but as we can see that the load generated is minimum in this case 1 so we can take model (8) as most efficient as it is producing very minimum load as compared to others.

2.2 Discussion of different models in case 2

Since we can conclude from the table 1, about the R-value & U-value of the walls. Greater the R-value greater will be the insulating power. Above result, we get the same temperature at same environment condition and same energy production but as we can see that the load generated is minimum in this case 2 so we can take model (14) as most efficient as it is producing very minimum load as compared to others and has also very less head loss among all. Since lesser the head loss greater will be the efficiency of the fluid system, here we can conclude that the model with minimum load have less head loss.

2.3 Discussion of different models in case 3

Since we can conclude from the table 1, about the R-value & U-value of the walls. Greater the R-value greater will be the insulating power. Above result, we get the same temperature at same environment condition and same energy production but as we can see that the load generated is minimum in this case 2 so we can take model (14) as most efficient as it is producing very minimum load as compared to others and has also very less head loss among all. Since lesser the head loss greater will be the efficiency of the fluid system, here we can conclude that the model with minimum load have less head loss.

Figure 3 Load on Most Efficient Model

III. CONCLUSION

  1. By performing the various tests for heating solutions using LOOPCAD 2019 software, the various different combinations were aligned through three different types of walls, floors and circuits i.e., walls- Frame wall or Partition wall, Foam Concrete Matrix and Block wall; floors- Concrete thin Slab, Gypsum Thin Slab and Heat Transfer Plate; circuit- Counterflow, Serpentine and Modulated Spiral respectively. Considering 3 cases comprising of 9 models each.
  2. In this analysis the loads were calculated, keeping the indoor temperature constant at 21°C among all the 27 models
  3. The efficient structures in terms of load are the Model no. 8, (wall- Foam Concrete Matrix, floor- Heat Transfer Plate and circuit- Counterflow). Model no.14 (wall- Foam Concrete Matrix, floor- Gypsum Thin Slab and circuit- Serpentine). and Model no. 23 (wall- Foam Concrete Matrix Wall, floor- Gypsum Thin Slab and circuit- Modulated Spiral).
  4. From the result we got the most efficient model among all the above mentioned three models model no. 14 with load being the minimum i.e., 6382 W with Head loss of 15.4 m/s2 is considered to be the most efficient among all the others.

  1. REFERENCES
  • Maivel, J. Kurnitski, Low temperature radiator heating distribution and emission efficiency in residential buildings, Energy Build. 69 (2014) 224–236. doi: 10.1016/j.enbuild.2013.10.030.
  • Richter, A. Meinzenbach, M. Knorr, LowEx Fernwärme - Multilevel district heating - Einfluss sinkender Vorlauftemperatur auf die gebäudetechnik [Multilevel district heating,The influence of lower supply temperature on the building installations], AGFW, Dresden, 2010.
  • Ait Msaad, M. Mahdaoui, T. Kousksou, A. Allouhi, T. El Rhafiki, A. Jamil, K. Ouazzani, Numerical simulation of thermal chaotic mixing in multiple rods rotating mixer, Case Stud. Therm. Eng. (2017) 388–398.
  • Hasan Karabay, MuslumArıcı, Murat Sandık, A numerical investigation of fluid flow and heat transfer inside a room for floor heating and wall heating systems, Energy Build. 67 (2013) 471–478.
  • ISO 7730:2005 ergonomics of the thermal environment-Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria, 2005.
  • Borong Lin, Zhe Wang, Hongli Sun, Yingxin Zhu, Qin Ouyang, Evaluation and comparison of thermal comfort of convective and radiant heating terminals In office buildings, Build. Environ. 106 (2016) 91–
  • Su Shin, Kyu Nam Rhee, Seong RyongRyu, Myoung Souk Yeo, Kwang Woo Kim, Design of radiant floor heating panel in view of floor surface temperatures, Build. Environ. 92 (2015) 559–577.
  • Muhammad Ahsan, Numerical analysis of friction factor for a fully developed turbulent flow using k-ε turbulence model with enhanced wall treatment, Beni-Suef Univ. J. Basic Appl. Sci. 3 (2014) 269–277.
  • ökhan Sevilgen, Muhsin Kilic, Numerical analysis of air flow, heat transfer, moisture transport and thermal comfort in a room heated by two-panel radiators, Energy Build. 43 (2017) 137–146.
  • Ran Gao, Angui Li a, Ou Zhang b, Hua Zhang, Comparison of indoor air temperatures of different under-floor heating pipe layouts, Energy Convers. Manag. 52 (2015) 1295–1304.
  • Xing Jin, Xiaosong Zhang, Yajun Luo, A calculation method for the floor surface temperature in radiant floor system, Energy Build. 42 (2010) 1753–1758.
  • Abdelaziz Laouadi, Development of a radiant heating and cooling model for building energy simulation software, Build. Environ. 39 (2004) 421–431.
Your portfolio, next

Ship work like this
in your own course.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.

Talk to a career counsellor

Free 20-minute call. We'll map the right course to where you want to work.

By submitting you agree to our Terms and Privacy Policy.