Identification of Cracks
1(A):
- OBSERVATION:
- By observing the picture shown we can understand that concrete suffered crushing due the impact of the force.
- And by concrete getting crushed we can also find reinforcement bars exposed out of the element.
- Though the element had such an impact it doesnot seem like there is severe damage to the element.
- The concrete in the element got spalled beyond the reinforcement which, as per observation from the image can be considered as the sign of rupture.
- Though the element is affected beneath its is clear in the top which seems to be the supportive effect of the flange adavantage from the slab.
- And other point is, if crack is developed from bottom to top it shows sense that rebar yielding can occur in support bottom only.
- Answer:
- From our observations we can come to a conclusion that,
- The failure occured may be a form of flexural failure due to reversal of stress during earthquake.
- During this stress reversal what happens is the support top experiences compression and the bottom support experiences tension.
- The main point here is that the top compression on the element was managed by the advantage of the support from the slab to the element.
- As we know steel reinforcement and the concrete combined as composite material acts as teh structural support for the buidling.
- As one of the material, the reinforcement got yielded this damage can be repaired.
1(B):
- OBSERVATION:
- In the shown image we can observe cracks along the edge of the beam and column.
- As like the older situation we are not finding any crushing of material or the element.
- But what we see is a crack due to some reason in the relation between the two elements.
- Though hard crushing or rupture is not found.
- We can see crack is developed through the structure and also teh crack seems wider.
- And the other major point is that the beam got separated from the column at joints.
- Which is not a good sign of good relation between the elements.
- And as told ealrier concrete is not severly crushed.
- Answer:
- As told in the observation there is poor realtion between the elemenst joining,
- We can come to a point that this is a beam pull out failure due to insufficient development length of reinforcement in joints.
- In severe case of teh earthquake at this same situation with severe horizontal movement of structure , the condition could have been worser.
- Like the beams could have got detached from the columns which is not at all acceptable by the structure leading to severe impact of the earthquake.
- Now after such happeening providing anchorage length between two existing concrete is very difficult and not advisable too.
- So this damage cannot be reapired.
1(C):
- OBSERVATION:
- In the case from the image we can see that the cracks in the structure are exactly at the joints of the column and the beam.
- And the crack has also got spread throught its entire width.
- And along with these elements the slab has also developed more craks along the beam width direction.
- Answer:
- After the observation, we can say that it is a plastic hinge failure.
- The damage here has occured only in the joint zone first of all.
- The damage at the joint may be due to cyclic lateral loading and stress reversal at the joints.
- And as we see the slab it has also participated to its best to handle the tension due to the force.
- This we could note because here slab is severly cracked which means it has undergone tension with its flange condition.
- But it could not control the damage.
- In this case teh joint can be strengthened.
QUESTION 2: What is the mode of failure or damage of the beams in the figure above? Are the damages repairable? Elaborate
Answer:
2(A):
- OBSERVATION:
- In the image given wecan find that , at the top of the column concrete has got damaged.
- And the concrete is seen damaged all around the face of teh column at the top of the column.
- And also we can find that the beams are safe.
- It seems the columns is placed at the edge of the building.
- And other important thing can be noted is. It seems like a openeing near the column.
- Which can be understood by absence of walls .
- It ccan probably be ground floor of the building , may left open for parking car and other movement access.
- Answer:
- So, it is understood from the image that it is a soft storey failure.
- Technically plastic hinge formation.
- As said before, due to absence of infill walls at the ground floor, The plastic hinge forms at teh top of ground storey columns during lateral movement.
- Based on the development of crush of concrete it can either be repairable or non repairable.
2(B):
- OBSERVATION:
- In the image supplied the damage seems worse.
- Here the concrete in teh element has developed complete breakage diagonally.
- As we can also see longitudinal reinforcements are intact but,
- Shear reinforcement spacing seems wider, which makes sense there may be lesser shear rebar provided.
- Answer:
- Here we can say it is a pure shear failure.
- Inadequate shear reinforcement certainly a reason for the concrete to take a high shear stress.
2(C):
- OBSERVATION:
- Here teh column completely failed.
- Majorly the failure seems to have happened at teh top of the column.
- And we can also find two slabs connected to teh column, probably one at mid height of the column.
- Here they have placed wooden supports whixh could be understood that may be post failure support.
- Which cannot be a perfect solution but a temporary support may be.
- This is to avoid complete collapse of the entire structure.
- Answer:
- Here we can say it is a short column failure.
- An additional beam or slab to teh mid height of the column makes teh column short on both remaining heights.
- Which may lead to short column failure.
- This type of failure is lead especially if the connection is unintentional and not accounted in design.
- The failure given in teh picture is not at all repairable